The Notifier® remote power supplies
FCPS-24S6/8 with battery charger include models with 6-amp and 8-amp 24-volt
remote power supplies. The FCPS-24S6E and FCPS-24S8E are remote power
supplies with a battery charger that connect to any 12 or 24 V fire alarm
control panel. They may also be utilized
as stand-alone power supplies with primary applications including notification
appliance circuit (NAC) expansion which supports ADA requirements. Notifier® remote power
supplies FCPS-24S6/8 may also
be used as auxiliary power to support 24 V system accessories.
Notifier® remote power supplies FCPS-24S6/8
provide filtered and regulated 24 VDC power to four notification appliance
circuits configured as class A or class B. Flexibility includes the
option to configure four outputs as all resettable, all non-resettable, or
split with two configured resettable and two non-resettable. The battery
charger is capable of charging up to 18 AH batteries.
FCPS-24S6/8 Benefits and Features
FCPS-24S6/8 benefits and features include:
- Ability to operate as either a “sync-generator” or “sync-follower”
- Two fully-isolated input/control circuits
- Compatible with coded inputs; signals passed through
- Four Class A (Style Z, with ZNAC-4 module) NACs or four Class B (Style Y)
- Fully filtered and regulated power output which is optimal to power four- annunciators, wire smoke detectors or other peripheral system equipment that requires filtered/regulated power.
- FCPS-24S6C & FCPS-24S8C are ULC-listed.
FCPS-24S6/8 Specifications
Primary (AC) Power:
·
FCPS-24S6C/-24S8C: 120
VAC, 60 Hz, 3.2A maximum
·
FCPS-24S6E/-24S8E: 240
VAC, 50 Hz, 1.6A maximum
·
Wire Size: minimum #14
AWG (2.0mm2) with 600 V insulation
Secondary Power (Battery) Charging Circuit:
·
Supports lead-acid
batteries only
·
Float-charge voltage:
27.6 VDC
·
Maximum current
charge: 1.5 A
·
Maximum battery
capacity: 18 AH
HRSS offers Notifier® remote power supplies with battery charger
and UL listed fire alarm system equipment and components. We provide
comprehensive fire and safety services including fire alarm system design,
testing, maintenance, repairs and monitoring. Contact us for assistance in
choosing the right fire alarm system and components for your fire protection
and safety.