The National Fire Alarm
Protection Association, NFPA, sets the standards and guidelines for fire and
safety system regulation. NFPA 72 is the
National Fire Alarm and Signaling Code which outlines the regulations for the
installation, application, inspection, performance, maintenance and testing
of fire alarm and emergency communications systems
and components. NFPA 72 outlines the spacing and location requirements of smoke
detectors and heat detectors.
While spacing reduction is
required for heat detectors in high ceilings, there are no specified
considerations for the placement of smoke detectors on high ceilings. There is inconsistency and confusion with
regard to smoke detectors where high ceilings are defined as more than ten feet
high. Clarification is needed on the
application of smoke detector spacing requirements in these applications.
Code requirements currently
state that the maximum distance between smoke detectors be a nominal 30 feet
and cannot exceed half of the spacing measured from the wall, with the location
on the ceiling required to be .7 times the nominal spacing. There is, however, no mention of ceiling
height although NFPA 72 does state that the effect of stratification below the
ceiling to be taken into consideration. An appendix to chapter 17 also states
that consideration should be given to installing aspirating smoke detectors at
various levels and using beam type of smoke detectors.
For greater clarification and
to ensure compliance, talk with your fire alarm and life safety systems specialists
at High Rise Security Systems. We are
recognized as an authority on fire alarm system design, installation and
maintenance, providing fire safety systems to commercial properties in and
around Chicago.
HRSS is a leading commercial fire alarm systems
consultant with vast knowledge in system design. We provide detailed fire alarm system design
in AutoCAD software, prepare datasheets for approval from your local AHJ and
guarantee code compliance. Contact us
today to learn more about NFPA 72 and the requirements for smoke detectors on
high ceilings.
No comments:
Post a Comment